产品详情
Switching-off thrust: 5000 to 45000 [N]
Operating speed: 10 to 120 [mm/min]
Operating stroke: 10 to 100 [mm]
Ambient temperature: -25 (-40) to +55 [°C]
Protection enclosure: IP 67
Operating position: any position
• Supply voltage 3x400, 3x380, 240, 220, 120, 24 V AC
• Terminal board connection
• Protection of the motor against overheating
• Switching off in limit positions from the position or thrust
• Adjustable switching-off thrust from 50% to 100%
• Torque (thrust) blocking in limit positions
• Torque (thrust) blocking during the start
• 2 freely programmable relays RE1, RE2
• Relay READY
• Control by unified signal 0/4 - 20 mA, 4 - 12 mA, 12 - 20 mA,
or 0/2 - 10 V (not for DMS3 in 2P version)
• Control voltage for remote control 24 V DC (Open-Stop-Close)
• Impulse control (inching duty)
• Timing mode / regime of operation
• Safety function ESD (failure reaction)
• Electronic position transmitter 4-20 mA passive (not for DMS3 in 2P version)
• Auxiliary voltage output 24 V DC, max. 40 mA for supply of the control inputs
• Output for failure messages
• Space heater operated by control unit
• LED position indicator
• Communication interface RS 232
• Programme for parameters setting by PC
• Mechanical position indicator
• Mechanical connection - pillar
• Manual control